Transformer example problem: Difference between revisions

From Class Wiki
Jump to navigation Jump to search
No edit summary
 
(44 intermediate revisions by 4 users not shown)
Line 1: Line 1:
===Problem:===
===Problem:===
An ideal transformer with a 300 turn primary connected to a 480 V, 60 Hz supply line is to output 120 V from the secondary. If a 100 Ω resistor is connected across the secondary, determine: A) How many turns the secondary must have. B) The current through the resistor, C)The current drawn through the primary.
An ideal transformer with a 300 turn primary connected to a 480 V, 60 Hz supply line needs to output 120 V from the secondary. If a 100 Ω resistor is connected across the secondary, determine: A) How many turns the secondary must have to output the desired voltage. B) The current through the resistor, C)The current drawn through the primary. D) The maximum flux in the core of the transformer
 
[[Image:Transformer_EMEC.png]]


===Solution:===
===Solution:===
Line 40: Line 42:
<br/>
<br/>
<br/>
<br/>
<math>\frac{i_1}{i_2} = \frac{75}{300}</math>
<math>\frac{i_1}{i_2} = \frac{N_2}{N_1}</math>
<br/>
<br/>
Where <math> i_1 = </math>Current in primary,
Where <math> i_1 = </math>Current in primary,
Line 46: Line 48:
<math>N_1 = </math> Number of turns in primary,
<math>N_1 = </math> Number of turns in primary,
<math>N_2 = </math> Number of turns in secondary
<math>N_2 = </math> Number of turns in secondary
<math>\frac{i_1}{1.2 \ A} = \frac{N_2}{N_1}</math>
 
 
<math>\frac{i_1}{1.2 \ A} = \frac{75 \ turns}{300 \ turns}</math>
 
Rearranging to solve for <math>i_1 </math>:
 
<math>\ i_1 = i_2 \cdot \frac{N_2}{N_1} \Rightarrow 1.2 A \cdot \frac{75 \ turns}{300 \ turns} \Rightarrow i_1 = .3 \ A</math>
 
====Part D:====
The induced emf of the secondary can be calculated by:
<math> V_2 = 4.44 \ \cdot  \mathit{f} \cdot N_2 \cdot \Phi_m \ \angle 0^\circ </math><ref>Guru and Huseyin, ''Electric Machinery and Transformers'', 3rd ed. (New York: Oxford University Press, 2001), 209.</ref>
Solving for <math> \Phi_m </math>, we can calculate the maximum flux in the core:
<math> \ \Phi_m = \frac{V_2}{4.44 \cdot \mathit{f} \cdot N_2} </math>
 
Where <math> \Phi_m \ = </math>max flux in core,
<math>V_2 = </math>Voltage across secondary,
<math>\mathit{f} = </math> Frequency of line,
<math>N_2 = </math> Number of turns in secondary
 
<math> \ \Phi_m = \frac{120}{4.44 \cdot 60 \ Hz \cdot 75} \Rightarrow \Phi_m = 6.006 \ mWb </math>
*Comment: There is a problem here in Part D, because in an ideal transformer <math>N_1 I_1 = N_2 I_2</math> and the flux from <math>I_2</math> opposes the flux from <math>I_1</math>.  Magnetic circuits tells us that the flux, <math>\Phi_1 = \frac{ N_1 I_1 }  \mathcal{R} </math>and the flux, <math>{\Phi_2} = \frac{-N_2 I_2} {\mathcal{R}}</math> so that the total flux in any ideal transformer is zero.
 
==References:==
<references/>
 
==Authors:==
[[Tim Rasmussen]]
==Reviewers:==
Wesley Brown
 
Alex Roddy
 
==Readers:==

Latest revision as of 13:25, 4 February 2010

Problem:

An ideal transformer with a 300 turn primary connected to a 480 V, 60 Hz supply line needs to output 120 V from the secondary. If a 100 Ω resistor is connected across the secondary, determine: A) How many turns the secondary must have to output the desired voltage. B) The current through the resistor, C)The current drawn through the primary. D) The maximum flux in the core of the transformer

Solution:

Part A:

The ratio of primary voltage to secondary voltage is directly proportional to the ratio of number of turns on the primary to number of turns on the secondary:

V1V2=N1N2

Where V1=Voltage across primary, V2=Voltage across secondary, N1= Number of turns in primary, N2= Number of turns in secondary


480volts120volts=300turnsN2

To solve for the number of turns required for the secondary, the equation is rearranged solving for N2=:

N2=300120480N2=75turns

Part B:

The voltage across the secondary is given in the problem statement as 120 volts. Using ohms law, V=iR, we can solve for the current in the loop (i2 ).
i2=V2RL
Where i2= Current through secondary, V2=Voltage across secondary, RL= Load Resistor (RL= 100 Ω)

i2=120volts100Ωi2=1.2A

Part C:

The ratio of primary current to secondary current is inversely proportional to the ratio of number of turns on the primary to number of turns on the secondary:

i1i2=N2N1
Where i1=Current in primary, i2=Current in secondary, N1= Number of turns in primary, N2= Number of turns in secondary


i11.2A=75turns300turns

Rearranging to solve for i1:

i1=i2N2N11.2A75turns300turnsi1=.3A

Part D:

The induced emf of the secondary can be calculated by: V2=4.44fN2Φm0<ref>Guru and Huseyin, Electric Machinery and Transformers, 3rd ed. (New York: Oxford University Press, 2001), 209.</ref> Solving for Φm, we can calculate the maximum flux in the core: Φm=V24.44fN2

Where Φm=max flux in core, V2=Voltage across secondary, f= Frequency of line, N2= Number of turns in secondary

Φm=1204.4460Hz75Φm=6.006mWb

  • Comment: There is a problem here in Part D, because in an ideal transformer N1I1=N2I2 and the flux from I2 opposes the flux from I1. Magnetic circuits tells us that the flux, Φ1=N1I1and the flux, Φ2=N2I2 so that the total flux in any ideal transformer is zero.

References:

<references/>

Authors:

Tim Rasmussen

Reviewers:

Wesley Brown

Alex Roddy

Readers: