Example: Step Down Transformer: Difference between revisions
Jump to navigation
Jump to search
Amy.crosby (talk | contribs) (New page: ==Problem Statement== Given a 48 kVA, 480/240 V/V step down transformer operating at rated load with a power factor of 0.7 (lag), determine the efficiency and voltage regulation. Given: <...) |
Amy.crosby (talk | contribs) No edit summary |
||
Line 2: | Line 2: | ||
Given a 48 kVA, 480/240 V/V step down transformer operating at rated load with a power factor of 0.7 (lag), determine the efficiency and voltage regulation. |
Given a 48 kVA, 480/240 V/V step down transformer operating at rated load with a power factor of 0.7 (lag), determine the efficiency and voltage regulation. |
||
Given: <math> R_L~=~0.2~\Omega,~~X_L~=~0.6~\Omega,~~ R_H~=~0.8~\Omega,~~X_H~=~1.6~\Omega,~~ R_{cH}~=~3.2~k\Omega,~~ |
Given: <math> R_L~=~0.2~\Omega,~~X_L~=~0.6~\Omega,~~ R_H~=~0.8~\Omega,~~X_H~=~1.6~\Omega,~~ R_{cH}~=~3.2~k\Omega,~~X_{mH}~=~1.2~k\Omega</math> |
||
*this problem is from EMEC EXAM 1, Winter 08 by legendary Dr. Cross |
*this problem is from EMEC EXAM 1, Winter 08 by legendary Dr. Cross |
||
==Solution== |
==Solution== |
||
From the given data of the step down transformer we can see that |
|||
<math>\text a=2~and~s=48000~\angle cos^{-1} \</math> |
Revision as of 01:06, 29 January 2010
Problem Statement
Given a 48 kVA, 480/240 V/V step down transformer operating at rated load with a power factor of 0.7 (lag), determine the efficiency and voltage regulation.
Given:
- this problem is from EMEC EXAM 1, Winter 08 by legendary Dr. Cross
Solution
From the given data of the step down transformer we can see that Failed to parse (syntax error): {\displaystyle \text a=2~and~s=48000~\angle cos^{-1} \}